Battery |
Description |
|
Normalspecification |
||
1 |
RatedVoltage |
51.2V |
2 |
RatedCapacity |
1000Ah |
3 |
RatedEnergy |
51.2KWH |
4 |
Battery Configuration |
10.24KWH(16S2P) *5PCS |
5 |
Battery Cell |
3.2V100AH160PCS |
StandardCharge |
||
1 |
Operationtemperaturerange@charging |
0~45℃ |
2 |
Ratedchargevoltage |
55.2±0.4V |
3 |
Maxchargevoltage |
56.8±0.4V |
4 |
Overcharge protection |
58.4±0.4V |
5 |
AllowedMAXchargecurrent(Total) |
550A withstand30s (every pack 110A) |
6 |
Peakchargecurrent(Total) |
600Awithstand5s (every pack 120A) |
7 |
Ratedchargecurrent(Total) |
500A (every pack 100A) |
8 |
Recommendchargecurrent(Total) |
<400A |
Standarddischarge |
||
1 |
Operationtemperaturerange@discharging |
-20~60℃ |
2 |
OutputVoltageRange |
40~56Vdc |
3 |
Recommend Working Range |
46~54Vdc |
4 |
Discharge Cut-offvoltage |
40V |
5 |
AllowedMAXdischargecurrent(Total) |
1100Awithstand30s (every pack 220A) |
6 |
Peakdischargecurrent(Total) |
1200Awithstand5s (every pack 240A) |
7 |
Rateddischargecurrent(Total) |
1000A (every pack 200A) |
8 |
Recommend dischargecurrent(Total) |
<800A |
Communication |
||
1 |
RS485 |
ForLCDremote |
2 |
CAN |
PCcontrolandmonitor |
Inverter (built-in) |
Description |
|
Normalspecification |
||
1 |
RatedPower |
15KW |
2 |
Output Waveform |
Pure Sine Wave/Same as input (Bypass Mode) |
3 |
Output Voltage |
240Vac(H-H)/120Vac(H-N) ±10% RMS |
4 |
Output Frequency |
50 or 60± 0.3Hz (Inverter mode by sw4 setting) |
5 |
Typical Transfer Time |
4-6ms typical,10ms(Max) |
6 |
THD |
< 3%(Rated voltage full R load) |
7 |
AC Input Range |
184-253Vac (UPS mode) or 140-270Vac (GEN mode) |
8 |
Customized AC Charger |
Battery type selector position 9, special design for LFP, make the battery cycle life Maximization |
9 |
MAX AC Charge Current |
100A |
10 |
Battery priority Function |
Setting by SW5 on position 1 (inverter mode valid), AC automatic come in when battery voltage low alarm at 48Vdc or 50Vdc |
11 |
AC Bypass without charging |
Battery type selector position 0 |
MPPT (built-in) |
Description |
|
Normalspecification |
||
1 |
PV POWER |
3.5KW*4 |
2 |
PV Input Voltage |
60-145Vdc |
3 |
MPPT Charging Voltage |
56.0Vdc (Fast charging)/54Vdc (Float charging) |
4 |
MPPT Output Current |
60A*4 |
Model |
Configuration |
|||
ESS15048E1000P4 |
MPPT |
INVERTER |
BATTERY |
Energy |
240A(60A*4) |
15KW |
1000AH(200AH*5) |
51.2kwh |
Mechanical Characteristics |
||||
ESS15048E1000P4 |
Dimension H*W*D |
Shipping H*W*D |
Weight(N.W.) |
Weight(G.W.) |
1810*560*960mm |
1960*700*1050mm |
700KG |
750KG |
Items |
Content (for each cell) |
Criterion |
Alarm LED(red) |
Over charge |
Over-chargewarning |
3700mv |
once/3s flash, keep output |
Over-charge protection |
3750mv |
once/1s flash, relay cut off |
|
Over-chargewarningrelease |
3400mv |
|
|
Over-charge protectionrelease |
3350mv |
|
|
Over-chargerelease method |
Discharging(Automatic) |
|
|
Over discharge |
Over-dischargewarning |
2700mv |
once/3s flash, keep output |
Over-discharge protection |
2500mv |
once/1s flash, relay cut off |
|
Over-dischargewarningrelease |
2900mv |
|
|
Over-discharge protectionrelease |
2800mv |
|
|
Over-dischargerelease method |
Charging |
|
|
Over current (CHG&DISCHG) |
Overcurrent warning |
110% rated |
once/1s flash, 30s off |
Overcurrent protection(PEAK) |
120% rated |
Lightning, delay 10s off relay cut off |
|
Overcurrentrelease method(CHG) |
Restart |
|
|
Overcurrentrelease method(DISCHG) |
Cut off loads and Restart |
|
|
Over & Lower Temp (Discharging) |
Overtemperature |
Warning@55℃ |
once/3s flash, keep output |
Protection@60℃ |
once/1s flash, relay cut off |
||
WarningRelease@40℃ |
|
||
ProtectionRelease@55℃ |
|
||
Lower temperature |
Warning@-20℃ |
once/3s flash, keep output |
|
Protection@-25℃ |
once/1s flash, relay cut off |
||
WarningRelease@-15℃ |
|
||
ProtectionRelease@-20℃ |
|
||
Over & Lower Temp(Charging) |
Overtemperature |
Warning@45℃ |
once/3s flash, keep output |
Protection@50℃ |
once/1s flash, relay cut off |
||
WarningRelease@40℃ |
|
||
ProtectionRelease@45℃ |
|
||
Lower temperature |
Warning@0℃ |
once/3s flash, keep output |
|
Protection@-5℃ |
once/1s flash, relay cut off |
||
WarningRelease@5℃ |
|
||
ProtectionRelease@0℃ |
|
Item |
Name |
Description |
1 |
INV power switch |
Power saver auto: inverter work in saver mode |
Inverter OFF: inverter power off |
||
Inverter ON: inverter work in normal mode |
||
2 |
Inverter indicator LED |
CHG: inverter working in battery charge mode |
INV: inverter working in battery discharge mode |
||
Alarm: inverter warning or fault |
||
3 |
LCD Screen |
Show the system working information |
4 |
Battery indicator LED |
RUN: battery working normal |
Alarm: battery warning or fault |
||
Display ON/OFF |
||
5 |
Button SYS |
Press button, LCD will show ESS info directly |
Button BATT |
Press button, LCD will show BATT info directly |
|
Button INV |
Press button, LCD will show INV info directly |
|
Button MPPT |
Press button, LCD will show MPPT info directly |
Charging-Power |
MPPT charging power total |
Energy-hour |
Solar generator energy in current hour |
Energy-Day |
Solar generator energy today |
Energy-Total |
Solar generator energy total |
AC Load |
Current AC loads power inverter take |
BAT-Voltage |
System battery voltage |
Total Bat capacity |
System rated battery capacity in total |
Remain Bat capacity |
System remain battery capacity in total |
Discharge-Time |
System estimated time to discharge battery empty in current condition |
Charge- Time |
System estimated time to charging battery full in current condition |
MPPT-Status |
All MPPT working status in system 00: normal 01: warning occur 02: fault occur |
Inverter-Status |
Inverter working status in system 00: normal 01: warning occur 02: fault occur |
Battery-Status |
All Battery working status in system 00: normal 01: warning occur 02: fault occur |
Total-battery pack |
Total battery packs in system |
Battery V: |
Current ID battery voltage |
Rated Cap: |
Battery rated capacity of current ID |
Current I: |
Positive means charge, Negative means discharge |
Current Cap: |
Remain capacity of current ID battery |
CHG time: |
Estimated time to charging battery full |
Current SOC: |
Remain SOC of current ID battery |
DIS time: |
Estimated time to discharge battery empty |
Cycle times: |
Battery cycle times of current ID |
ID: |
Current battery identity number |
Alarm status: |
Ref the battery pack alarm code table |
OVP times |
Number of battery voltage alarm times |
OCP times |
Number of battery current alarm times |
OTP times |
Number of battery temperature alarm times |
0000 |
normal |
0100 |
Cell Over-voltage Warning |
0200 |
Cell Over-voltage Protection |
0400 |
Cell Low-voltage Warning |
0800 |
Cell Low-voltage Protection |
0010 |
Cell Over-temp Warning |
0020 |
Cell Over-temp Protection |
0040 |
Cell Low-temp Warning |
0080 |
Cell Low-temp Protection |
0001 |
Discharge Over-current Warning |
0002 |
Discharge Over-current Protection |
0004 |
Charge Over-current Warning |
0008 |
Charge Over-current Protection |
ID |
Current battery identity number |
C1——C16 |
Internal cells voltage |
T1——T4 |
Internal temperature detecting value |
Max V |
Maximum cell voltage |
Min V |
Minimum cell voltage |
Max T |
Maximum internal temperature detecting value |
Min T |
Minimum internal temperature detecting value |
Rated-Power |
Inverter rated power |
Input AC |
Current utility or generator AC voltage |
Output AC |
Inverter output AC voltage |
Batt DC |
Current battery voltage |
Output Freq |
Inverter output AC frequency |
Output Load |
Current AC loads percentage inverter take |
Work mode |
Charging or Inverter |
Mode Transfer times |
Inverter working mode transfer times |
Alarm |
Ref inverter 3.3.9 |
Fault |
Ref inverter 3.3.9 |
ID |
Current MPPT identity number |
PV Input Voltage |
Current MPPT PV input voltage |
Charging Current |
Current MPPT charging current |
Charging Power |
Current MPPT charging power |
Charge Voltage |
Current MPPT charging voltage |
Unit HS Temperature |
Current MPPT internal temperature |
Warning code |
Ref MPPT 3.1.3 |
Fault code |
Ref MPPT 3.1.3 |
Fault times |
Current MPPT occurs fault times |
Battery |
Description |
|
Normalspecification |
||
1 |
RatedVoltage |
51.2V |
2 |
RatedCapacity |
1000Ah |
3 |
RatedEnergy |
51.2KWH |
4 |
Battery Configuration |
10.24KWH(16S2P) *5PCS |
5 |
Battery Cell |
3.2V100AH160PCS |
StandardCharge |
||
1 |
Operationtemperaturerange@charging |
0~45℃ |
2 |
Ratedchargevoltage |
55.2±0.4V |
3 |
Maxchargevoltage |
56.8±0.4V |
4 |
Overcharge protection |
58.4±0.4V |
5 |
AllowedMAXchargecurrent(Total) |
550A withstand30s (every pack 110A) |
6 |
Peakchargecurrent(Total) |
600Awithstand5s (every pack 120A) |
7 |
Ratedchargecurrent(Total) |
500A (every pack 100A) |
8 |
Recommendchargecurrent(Total) |
<400A |
Standarddischarge |
||
1 |
Operationtemperaturerange@discharging |
-20~60℃ |
2 |
OutputVoltageRange |
40~56Vdc |
3 |
Recommend Working Range |
46~54Vdc |
4 |
Discharge Cut-offvoltage |
40V |
5 |
AllowedMAXdischargecurrent(Total) |
1100Awithstand30s (every pack 220A) |
6 |
Peakdischargecurrent(Total) |
1200Awithstand5s (every pack 240A) |
7 |
Rateddischargecurrent(Total) |
1000A (every pack 200A) |
8 |
Recommend dischargecurrent(Total) |
<800A |
Communication |
||
1 |
RS485 |
ForLCDremote |
2 |
CAN |
PCcontrolandmonitor |
Inverter (built-in) |
Description |
|
Normalspecification |
||
1 |
RatedPower |
15KW |
2 |
Output Waveform |
Pure Sine Wave/Same as input (Bypass Mode) |
3 |
Output Voltage |
240Vac(H-H)/120Vac(H-N) ±10% RMS |
4 |
Output Frequency |
50 or 60± 0.3Hz (Inverter mode by sw4 setting) |
5 |
Typical Transfer Time |
4-6ms typical,10ms(Max) |
6 |
THD |
< 3%(Rated voltage full R load) |
7 |
AC Input Range |
184-253Vac (UPS mode) or 140-270Vac (GEN mode) |
8 |
Customized AC Charger |
Battery type selector position 9, special design for LFP, make the battery cycle life Maximization |
9 |
MAX AC Charge Current |
100A |
10 |
Battery priority Function |
Setting by SW5 on position 1 (inverter mode valid), AC automatic come in when battery voltage low alarm at 48Vdc or 50Vdc |
11 |
AC Bypass without charging |
Battery type selector position 0 |
MPPT (built-in) |
Description |
|
Normalspecification |
||
1 |
PV POWER |
3.5KW*4 |
2 |
PV Input Voltage |
60-145Vdc |
3 |
MPPT Charging Voltage |
56.0Vdc (Fast charging)/54Vdc (Float charging) |
4 |
MPPT Output Current |
60A*4 |
Model |
Configuration |
|||
ESS15048E1000P4 |
MPPT |
INVERTER |
BATTERY |
Energy |
240A(60A*4) |
15KW |
1000AH(200AH*5) |
51.2kwh |
Mechanical Characteristics |
||||
ESS15048E1000P4 |
Dimension H*W*D |
Shipping H*W*D |
Weight(N.W.) |
Weight(G.W.) |
1810*560*960mm |
1960*700*1050mm |
700KG |
750KG |
Items |
Content (for each cell) |
Criterion |
Alarm LED(red) |
Over charge |
Over-chargewarning |
3700mv |
once/3s flash, keep output |
Over-charge protection |
3750mv |
once/1s flash, relay cut off |
|
Over-chargewarningrelease |
3400mv |
|
|
Over-charge protectionrelease |
3350mv |
|
|
Over-chargerelease method |
Discharging(Automatic) |
|
|
Over discharge |
Over-dischargewarning |
2700mv |
once/3s flash, keep output |
Over-discharge protection |
2500mv |
once/1s flash, relay cut off |
|
Over-dischargewarningrelease |
2900mv |
|
|
Over-discharge protectionrelease |
2800mv |
|
|
Over-dischargerelease method |
Charging |
|
|
Over current (CHG&DISCHG) |
Overcurrent warning |
110% rated |
once/1s flash, 30s off |
Overcurrent protection(PEAK) |
120% rated |
Lightning, delay 10s off relay cut off |
|
Overcurrentrelease method(CHG) |
Restart |
|
|
Overcurrentrelease method(DISCHG) |
Cut off loads and Restart |
|
|
Over & Lower Temp (Discharging) |
Overtemperature |
Warning@55℃ |
once/3s flash, keep output |
Protection@60℃ |
once/1s flash, relay cut off |
||
WarningRelease@40℃ |
|
||
ProtectionRelease@55℃ |
|
||
Lower temperature |
Warning@-20℃ |
once/3s flash, keep output |
|
Protection@-25℃ |
once/1s flash, relay cut off |
||
WarningRelease@-15℃ |
|
||
ProtectionRelease@-20℃ |
|
||
Over & Lower Temp(Charging) |
Overtemperature |
Warning@45℃ |
once/3s flash, keep output |
Protection@50℃ |
once/1s flash, relay cut off |
||
WarningRelease@40℃ |
|
||
ProtectionRelease@45℃ |
|
||
Lower temperature |
Warning@0℃ |
once/3s flash, keep output |
|
Protection@-5℃ |
once/1s flash, relay cut off |
||
WarningRelease@5℃ |
|
||
ProtectionRelease@0℃ |
|
Item |
Name |
Description |
1 |
INV power switch |
Power saver auto: inverter work in saver mode |
Inverter OFF: inverter power off |
||
Inverter ON: inverter work in normal mode |
||
2 |
Inverter indicator LED |
CHG: inverter working in battery charge mode |
INV: inverter working in battery discharge mode |
||
Alarm: inverter warning or fault |
||
3 |
LCD Screen |
Show the system working information |
4 |
Battery indicator LED |
RUN: battery working normal |
Alarm: battery warning or fault |
||
Display ON/OFF |
||
5 |
Button SYS |
Press button, LCD will show ESS info directly |
Button BATT |
Press button, LCD will show BATT info directly |
|
Button INV |
Press button, LCD will show INV info directly |
|
Button MPPT |
Press button, LCD will show MPPT info directly |
Charging-Power |
MPPT charging power total |
Energy-hour |
Solar generator energy in current hour |
Energy-Day |
Solar generator energy today |
Energy-Total |
Solar generator energy total |
AC Load |
Current AC loads power inverter take |
BAT-Voltage |
System battery voltage |
Total Bat capacity |
System rated battery capacity in total |
Remain Bat capacity |
System remain battery capacity in total |
Discharge-Time |
System estimated time to discharge battery empty in current condition |
Charge- Time |
System estimated time to charging battery full in current condition |
MPPT-Status |
All MPPT working status in system 00: normal 01: warning occur 02: fault occur |
Inverter-Status |
Inverter working status in system 00: normal 01: warning occur 02: fault occur |
Battery-Status |
All Battery working status in system 00: normal 01: warning occur 02: fault occur |
Total-battery pack |
Total battery packs in system |
Battery V: |
Current ID battery voltage |
Rated Cap: |
Battery rated capacity of current ID |
Current I: |
Positive means charge, Negative means discharge |
Current Cap: |
Remain capacity of current ID battery |
CHG time: |
Estimated time to charging battery full |
Current SOC: |
Remain SOC of current ID battery |
DIS time: |
Estimated time to discharge battery empty |
Cycle times: |
Battery cycle times of current ID |
ID: |
Current battery identity number |
Alarm status: |
Ref the battery pack alarm code table |
OVP times |
Number of battery voltage alarm times |
OCP times |
Number of battery current alarm times |
OTP times |
Number of battery temperature alarm times |
0000 |
normal |
0100 |
Cell Over-voltage Warning |
0200 |
Cell Over-voltage Protection |
0400 |
Cell Low-voltage Warning |
0800 |
Cell Low-voltage Protection |
0010 |
Cell Over-temp Warning |
0020 |
Cell Over-temp Protection |
0040 |
Cell Low-temp Warning |
0080 |
Cell Low-temp Protection |
0001 |
Discharge Over-current Warning |
0002 |
Discharge Over-current Protection |
0004 |
Charge Over-current Warning |
0008 |
Charge Over-current Protection |
ID |
Current battery identity number |
C1——C16 |
Internal cells voltage |
T1——T4 |
Internal temperature detecting value |
Max V |
Maximum cell voltage |
Min V |
Minimum cell voltage |
Max T |
Maximum internal temperature detecting value |
Min T |
Minimum internal temperature detecting value |
Rated-Power |
Inverter rated power |
Input AC |
Current utility or generator AC voltage |
Output AC |
Inverter output AC voltage |
Batt DC |
Current battery voltage |
Output Freq |
Inverter output AC frequency |
Output Load |
Current AC loads percentage inverter take |
Work mode |
Charging or Inverter |
Mode Transfer times |
Inverter working mode transfer times |
Alarm |
Ref inverter 3.3.9 |
Fault |
Ref inverter 3.3.9 |
ID |
Current MPPT identity number |
PV Input Voltage |
Current MPPT PV input voltage |
Charging Current |
Current MPPT charging current |
Charging Power |
Current MPPT charging power |
Charge Voltage |
Current MPPT charging voltage |
Unit HS Temperature |
Current MPPT internal temperature |
Warning code |
Ref MPPT 3.1.3 |
Fault code |
Ref MPPT 3.1.3 |
Fault times |
Current MPPT occurs fault times |
Welcome to our website. If you have any requests or suggestions,please feel free to email us at yiyen@yiyen.com or use the following enquiry form. Please allow us to provide you with the best service.
Welcome to our website. If you have any requests or suggestions,please feel free to email us at yiyen@yiyen.com or use the following enquiry form. Please allow us to provide you with the best service.